Juno Technical Information
Dimensions & Cable Capacities
| Data Cable Diameter |
Nominal
CSA |
Compartment A |
| 4609mm² |
4116mm² & 25mm Back Box (2420mm²) |
4116mm² & 35mm Back Box (1700mm²) |
| |
|
45% Fill (2074mm²) |
45% Fill (1309mm²) |
45% Fill (984mm²) |
| 5mm |
19.6mm² |
94 |
55 |
39 |
| 5.5mm |
23.8mm² |
77 |
45 |
32 |
| 6mm |
28.3mm² |
65 |
38 |
27 |
| 6.5mm |
33.2mm² |
55 |
32 |
23 |
| 7mm |
38.5mm² |
48 |
28 |
19 |
| Power Cable Conductor CSA |
Cable
Factor |
Compartment A |
| 4609mm² |
4116mm² & 25mm Back Box (2420mm²) |
4116mm² & 35mm Back Box (1700mm²) |
| |
|
45% Fill (2074mm²) |
45% Fill (1309mm²) |
45% Fill (984mm²) |
| 1.5mm² |
8.6 |
215 |
126 |
88 |
| 2.5mm² |
12.6 |
144 |
85 |
59 |
| 4mm² |
16.6 |
111 |
65 |
46 |
| 6mm² |
21.2 |
87 |
51 |
36 |
Typical cable loading information in line with wiring regulation BS 7671 (45% CSA Fill)
|