Elite 3 Technical Information
Dimensions & Cable Capacities
| Data Cable Diameter |
Nominal
CSA |
Compartment A
2070mm² |
Compartment B |
Compartment C
2070mm² |
| 3590mm² |
3590mm² & 25mm Box |
3590mm² & 35mm Box |
| |
|
45% Fill (928mm²) |
45% Fill (1615mm²) |
45% Fill (813mm²) |
45% Fill (488mm²) |
45% Fill (928mm²) |
| 5mm |
19.6mm² |
47 |
82 |
41 |
24 |
47 |
| 5.5mm |
23.8mm² |
38 |
67 |
34 |
20 |
38 |
| 6mm |
28.3mm² |
32 |
57 |
28 |
17 |
32 |
| 6.5mm |
33.2mm² |
28 |
48 |
24 |
14 |
28 |
| 7mm |
38.5mm² |
24 |
41 |
21 |
12 |
24 |
| 8mm |
50.3mm² |
18 |
32 |
16 |
9 |
18 |
| 9mm |
63.6mm² |
14 |
25 |
12 |
7 |
14 |
| 10mm |
78.5mm² |
11 |
20 |
10 |
6 |
11 |
| Power Cable Conductor CSA |
Cable
Factor |
Compartment A
2070mm² |
Compartment B |
Compartment C
2070mm² |
| 3590mm² |
3590mm² & 25mm Box |
3590mm² & 35mm Box |
| |
|
45% Fill (928mm²) |
45% Fill (1615mm²) |
45% Fill (813mm²) |
45% Fill (488mm²) |
45% Fill (928mm²) |
| 1.5mm² |
8.6 |
107 |
187 |
98 |
61 |
107 |
| 2.5mm² |
12.6 |
73 |
126 |
67 |
41 |
73 |
| 4mm² |
16.6 |
55 |
97 |
51 |
31 |
55 |
| 6mm² |
21.2 |
43 |
76 |
40 |
25 |
43 |
Typical cable loading information in line with wiring regulation BS 7671 (45% CSA Fill)
| Standards |
ELITE 3 trunking system meets and exceeds the requirements for:
BS6701, ISO/IEC11801(ED2.0 Amd 2) and
Cenelec (BSEN50173 Part 1 / 2, BSEN50174-2) BS4678 Pt 4, BS7671 (IEE regs) |
|